For firealarm connections in electronic fire control systems and for connection of telecommunication and data transmission systems.
Suitable for fixed indoor installations. Not recommended for underground installation.
Technical characteristics:
Produced according to DIN VDE 0815
Conductor diameter: 0.60 mm and 0.80 mm
Loop resistance at +20 0C, max.:
For 0.6 mm: 130 Ohm/km
For 0.8 mm: 73.2 Ohm/km
Insulation resistance at +20 0C: 100 MOhm.km
Peak working voltage: 300 V
Test voltage:
Between the cores of the active pair: 800 V
Between cores and screen: 800 V
Nominal capacitance at frequency 800 Hz: max. 100 nF/km
Temperature range: from -30 °C to +70 °C
Minimum single time bending radius during installation: 10 D
Capacitance unbalance k1 80% between pairs at frequency 800 Hz: 300 pF/100 m
Attenuation (800 Hz):
For 0.6 mm: 1.7 dB/km
For 0.8 mm: 1.1 dB/km
Flame retardance: flame retardant acc. to IEC 60332-1
Sheath colour: Red, RAL 3000
Cable design:
Solid bare copper conductors with diameter 0.60 mm and 0.80 mm
Insulation: PVC
Bunch of twisted pairs
Core wrapping with separating polyester tape
Electrostatic screen of plastic coated AL foil with drain copper wire with diameter: